About this calculator
What it does
Given a solar panel's datasheet values and your solar generator's MPPT input limits, this tool enumerates every series × parallel combination, filters out those that violate voltage, current, or start-voltage limits, and ranks the survivors by total power and headroom.
Formulas
- cold_Voc = Voc × (1 + tempCoef% × (T_min − 25°C))
- string_Vmp = series × Vmp
- string_cold_Voc = series × cold_Voc
- total_Isc = parallel × Isc
- total_W = series × parallel × W_panel
Validity rules
- string_cold_Voc ≤ MPPT max PV voltage (hard limit)
- total_Isc ≤ MPPT max PV current (hard limit)
- string_Vmp ≥ MPPT minimum start voltage
- total_W ≤ MPPT max PV power (soft — over-paneling flagged but allowed; MPPT clips)
Assumptions & caveats
- STC values are used for power; real-world output is typically 70–85% of STC.
- Voltage drop from wiring is not modeled. For long runs, add 3–5% margin.
- Voc temperature coefficient defaults to −0.29 %/°C — check your datasheet.
- Always verify recommended wiring against your generator's manual before connecting.